Mô tả
1 phase 24 V DC/10 ATRIO-PS/1AC/24DC/10
Input data
Nominal input voltage range |
100 V AC … 240 V AC |
Input voltage range |
85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V) |
Dielectric strength maximum |
300 V AC |
AC frequency range |
45 Hz … 65 Hz |
Discharge current to PE |
< 3.5 mA |
Current consumption |
3 A (100 V AC) |
|
1.5 A (240 V AC) |
Nominal power consumption |
272 VA |
Inrush current |
< 15 A |
Mains buffering time |
> 24 ms (120 V AC) |
|
> 24 ms (230 V AC) |
Input fuse |
6.3 A (slow-blow, internal) |
Recommended breaker for input protection |
10 A … 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) |
0.99 |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Back to top
Output data
Nominal output voltage |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
10 A (UOUT = 24 V DC) |
Derating |
55 °C … 70 °C (2.5%/K) |
Connection in parallel |
Yes, for redundancy and increased capacity |
Connection in series |
yes |
Feedback voltage resistance |
35 V DC |
Protection against overvoltage at the output (OVP) |
< 35 V DC |
Max. capacitive load |
unlimited |
Active current limitation |
Approx. 14 A (for short-circuit) |
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 2 % (change in load, dynamic 10 % … 90 %) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 10 mVPP |
Output power |
240 W |
Typical response time |
< 1 s |
Peak switching voltages nominal load |
< 50 mVPP |
Maximum power dissipation in no-load condition |
6.7 W |
Power loss nominal load max. |
30 W |
Đánh giá
Chưa có đánh giá nào.