Mô tả
Model 1734-AENTR
Indicators 3 red/green status indicators on CPU:
– Module status
– Network status (Ports 1 and 2 combined)
– PointBus status
1 green/yellow status indicator on CPU:
– Network activity (Ports 1 and 2 combined)
2 green/yellow status indicators on base:
– Link 1 activity/status
– Link 2 activity/status
2 green power supply status indicators on DC-DC Converter:
– System power (5V DC to PointBus Out)
– Field power (24V DC from Field In)
Power consumption 10.4 W max @ 28.8V DC
Power dissipation 6.3 W max @ 28.8V DC
Input overvoltage protection Reverse polarity protected
Thermal dissipation 21.5 BTU/hr max @ 28.8V DC
Isolation voltage 50V (continuous), Basic Insulation Type, Network to Power, Network to Backplane, Power to Backplane, and
Network to Network.
Type tested at 1930V DC for 60 s
Field power supply 10 28.8V DC, 10A max
Field power output 10 28.8V DC, 9A max
Module input 10 28.8V DC, 1000 mA
PointBus output 5V DC, 0.8A max
Dimensions (HxWxD), approx 76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.)
Enclosure type rating None (open-style)
Terminal base screw torque 0.8 Nm (7 lb-in)
Weight, approx. 280 g (0.62 lb)
Wiring category¹ 1 – on power ports
2 – on communications ports
Wire size Power connections:
0.34 2.1 mm² (22 14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.)
insulation max
Ethernet connections:
RJ-45 connector according to IEC 60603-7, 2 or 4 pair
Category 5e minimum cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702
North American temp code T4
IEC temp code T4
Đánh giá